• Share on :
  • Facebook
  • Twitter
  • Google PLus
  • Partager par mail

Type 1 PV surge protector : DS50PV/12KT1

DS50PV-G/12KT1 Type 1+2 PV surge protector Iimp 6.25 kA

DS50PV-1000G/12KT1

- Type 1+2 surge protector for Photovoltaic
- Impulse currents Iimp/Itotal : 6.25/12.5 kA (10/350µs)
- Common/Differential mode protection
- Remote signaling (option)
- EN 50539-11 compliance

Download the datasheet Contact us

Select a reference :

Citel model : DS50PV-1000G/12KT1

Part Number : 482383

Click on the blocks to display detailed characteristics

Electrical characteristics
View details
Hide details
SPD type
follow test IEC 61643-11
1+2
Network
PV network 1000 Vdc
PV Network voltage
Uocstc
1000 Vdc
Max. PV operating voltage
Ucpv
1200 Vdc
Permanent Operating current
Current consumption at Ucpv
Icpv
<0.1 mA
Residual Current
LeakAge current at Uc
Ipe
none
Follow current
If
none
Nominal discharge current
15 x 8/20 µs impulses
In
15 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
Imax
40 kA
Total Maximal discharge current
max. total withstand @ 8/20 µs
Imax Total
60 kA
Impulse current by pole
max. withstand 10/350µs by pole
Iimp
6,25 kA
Total lightning current
max. total withstand @ 10/350 µs
Itotal
12,5 kA
Current withstand short circuit PV
Iscwpv
15000 A
Connection mode
+/-/PE
Protection mode(s)
MC/MD
Protection level CM/DM
@In (8/20µs) and @ 6kV (1.2/50µs)
Up mc/md
2.6/4.6 kV
Mechanical characteristics
View details
Hide details
Connection to Network
Screw terminals: 2.5-25mm²
Format
Plug-in modular box
Mounting
Symmetrical rail 35 mm (EN60715)
Housing material
Thermoplastic UL94-V0
Operating temperature
-40/+85°C
Protection rating
IP20
Outdoor application
N
Disconnection indicator
2 mechanical indicators
Spare module
DSM50PV-1000G/12KT1
Remote signaling of disconnection
Option DS50PVS-1000G/12KT1 - output on changeover
Associated disconnection devices
View details
Hide details
Thermal disconnector
internal
Fuses
sans
Standards compliance
View details
Hide details
Standards compliance EN 50539-11