The Different Parameters of a Surge Protective Device (SPD)
Low-voltage network surge protective devices are defined by a set of electrical characteristics, specified in the NF EN 61643-11 standard, which help the user select the most suitable product for their application
Continuous Operating Voltage - Uc | The maximum continuous operating voltage $U_c$ is the maximum root-mean-square (rms) AC voltage that can be continuously applied to the SPD, including a safety margin. |
Temporary Overvoltage - Ut | The temporary overvoltage Ut (TOV) is the maximum rms value acceptable by the SPD for 5 seconds and 120 minutes, either in withstand mode or in a controlled end-of-life mode (disconnection). The Ut parameter is higher than the Ut voltage. |
Discharge current - In and Imax | The maximum discharge current Imax, applicable to Type 2 SPDs, corresponds to the maximum withstand capacity of an SPD without destruction when subjected to a single lightning stroke (8/20 μs wave). The nominal discharge current In corresponds to the repetitive withstand capacity without destruction (15 strokes of an 8/20 μs wave) of a Type 1 or Type 2 SPD. |
Impulse current - Iimp | The impulse current Iimp applicable to Type 1 SPDs, corresponds to the maximum withstand capacity without destruction when subjected to 1 lightning stroke (10/350 μs wave). This test simulates the consequences of a direct lightning strike on the installation. |
Total discharge current - Itotal | The total discharge current flowing through the PE or PEN conductor of a multipole SPD. |
Specific energy - W/R | The energy dissipated during the discharge of the $I_{imp}$ impulse current during the Class I test. It is expressed in kJ/ohm. |
Open circuit voltage - Uoc | This parameter only applies to Type 3 SPDs and corresponds to the maximum acceptable combined wave voltage (maximum value = 20 kV). |
Protectio level - Up | The maximum value of the residual voltage across the SPD terminals during the 8/20 μs current wave test (at the highest value of the declared In or Imp currents) or during the 1.2/50 μs voltage wave test @ 6 kV (if required). |
Residual voltage | The value of the residual voltage across the SPD terminals when subjected to an 8/20 μs current wave of a specific value (e.g., 5 kA). |
Short-Circuit Current Rating - Isccr | The SPD and its associated disconnecting device (fuse) are tested to safely disconnect up to a maximum short-circuit current value (e.g., 50 kA). This $I_{sccr}$ value must be higher than the prospective short-circuit current of the network at the installation point of the SPD. |
Follow Current Interrupting Rating - Ifi | This criterion applies exclusively to "air spark gap" technology SPDs. After triggering, these SPDs conduct a portion of the network current (follow current) and must be able to interrupt it. This behavior does not apply to low-voltage SPDs based on "varistor" technology |
Maximum DC Voltage- Ucpv | The voltage applicable to the SPD under continuous operating conditions. It must be higher than the maximum PV voltage (Uocstc). |
Short-Circuit Current Rating - Iscpv | The SPD must safely withstand (disconnect) an end-of-life test at a declared short-circuit current value. This $I_{scpv}$ value must be higher than the maximum short-circuit current of the PV line ($I_{scstc}$). |