Coaxial surge protector DC-3.5 GHz
Part Number: 60001
P8AX09-N/MF
- RF coaxial surge protector
- 3.5 GHz
- Connectors: N
- Low insertion loss
- Removable GDT
- DC-pass
- Bi-directional protection
- Conforms to IEC/EN 61643-21
- SPD categories D1, C3, C2
|
Lightning Protection Zones (LPZ)
|
0 - 3 |
|
|
Max. DC operating voltage
|
Uc | 72 Vdc |
|
Frequency range
|
f | DC-3.5 GHz |
|
Insertion loss
|
< 0.2 dB |
|
|
Return loss
|
> 20 dB |
|
|
Impedance
|
50 ohms |
|
|
VSWR
|
<1.2:1 |
|
|
Max. load current @25°C
|
IL | 10 A |
|
Residual Current
Leakage current to Ground
|
Ipe | None |
|
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 20 kA |
|
Nominal discharge current
C2 (1.2/50us / 8/20µs), 10 applications X-C (Line/Earth)
|
In | 10 kV / 5 kA |
|
Protection Level
C2 (1.2/50µs / 8/20µs), 10 applications, Y-C (Line-Earth)
|
Up | < 1000 V |
|
Protection Level
C3 (10/1000μs), 300 applications@10 A, Y-C (Line/Earth)
|
Up | < 700 V |
|
Impulse current
D1 (10/350μs), 2 applications, X-C (Line/Earth)
|
Iimp | 500 A |
|
Max RF Power
|
25 W |
|
|
Typical let through energy
(50 ohms) input 4kV 1.2/50μs - 2kA 8/20μs
|
300 µJ |
|
|
DC Pass
|
Yes |
|
|
Insulation resistance
|
IR | ≥10 GOhms |
|
Capacitance
@1MHz, X-C (Line/Earth)
|
C | < 6 pF |
|
Technology
|
Gas discharge tube |
|
|
Connection to Network
|
Connector N Male/Female |
|
|
Mounting
|
Bulkhead or Bracket |
|
|
Housing material
|
Brass/Surface plating: Cu Zn Sn |
|
|
Operating temperature
|
Tu | -40/+85°C |
|
Relative Humidity
|
5 - 85% |
|
|
Ingress Protection rating
|
IP65 (NEMA 4) |
|
|
Failsafe mode
|
Transmision cut-off - fault mode 2 (short circuit) |
|
|
Disconnection indicator
|
Transmision interrupt |
|
|
Spare module(s)
|
BBHF-90V |
|
|
Dimensions
|
See diagram |
|
|
Contacts
|
Bronze/Surface Au-Ag |
|
|
Weight
|
0.146 kg / 0.32 lbs |
|
Standards compliance
|
IEC 61643-21 / EN 61643-21 / UL497E |
|
|
UL Category
|
QVLA - Antenna lead-in conductors |
|
|
UL File Number
|
E349646 |
|
|
Environmental standards
|
EU RoHS |
Datasheet